BZXVX - HALON 1301 & GLC-13B1
- MSDS: BZXVX
- Manufacturer: GREAT LAKES CHEMICAL CORP
- Product Name: HALON 1301 & GLC-13B1
- National Stock Number: 4210-01-358-7686
Product Identification
Product ID:HALON 1301 & GLC-13B1
MSDS Date:06/01/1993
FSC:4210
NIIN:01-358-7686
MSDS Number: BZXVX
Responsible Party
WEST LAFAYETTE, IN 47906-5000
US
Emergency Phone: 317-463-2511
Info Phone: 317-463-2511
Cage: 2E394
Contractor
Telephone: 765-497-6100/800-949-5167
Cage: 2E394
Ingredients
BROMOTRIFLUOROMETHANE
CAS: 76-63-8
RTECS: PA5425000
Hazards
Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:HALON 1301 & GLC-13B1 HAS ANESTHETIC &
CARDIAC EFFECTS AT CONCENTRATIONS >10% BY VOLUME, CONCENTRATIONS
<10%. PROLONGED EXPOSURE TO CONCENTRATIONS >10% MAY LEAD TO
UNCONSCIOUSNESS & POSSIBLY DEATH.
Explanation of Carcinogenicity:NONE
Effects of Overexposure:IRRITATION, MILD INTOXICATION, UNCONSCIOUSNESS.
Medical Cond Aggravated by Exposure:CARDIAC CONDITIONS.
First Aid
First Aid:INHALATION: REMOVE TO FRESH AIR. GIVE CPR/OXYGEN IF NEEDED.
SKIN/EYES: FLUSH W/WATER. OBTAIN MEDICAL ATTENTION IN ALL CASES.
NOTE: EPINEPHRINE IS CONTRAINDICATED IN THE TREATMENT OF
OVER-EXPOSURE TO T HIS PRODUCT.
Fire Fighting
Flash Point:NON-FLAMMABLE
Extinguishing Media:USE MEDIA SUITABLE FOR FLAMMABLE MATERIALS IN THE
AREA.
Fire Fighting Procedures:USE WATER SPRAY TO COOL CYLINDERS. WEAR SELF
CONTAINED BREATHING APPARATUS.
Unusual Fire/Explosion Hazard:PREDOMINANT DECOMPOSITION PRODUCTS ARE
HYDROGEN FLUORIDE & HYDROGEN BROMIDE IN FIRE SITUATIONS. PRODUCT IS
IRRITATING & POTENTIALLY TOXIC.
Accidental Release
Spill Release Procedures:EVACUATE AREA. WEAR SELF CONTAINED BREATHING
APPARATUS. VENTILATE ENCLOSED AREAS IN CASE OF DISCHARGE.
Handling
Handling and Storage Precautions:PROTECT CYLINDERS FROM PHYSICAL
DAMAGE. STORAGE TEMP SHOULDN'T EXCEED 125F. CYLINDERS SHOULD BE
SECURED FOR STORAGE W/VALVE PROTECTION CAP IN PLACE.
Other Precautions:AVOID EXPOSURE TO PRODUCT & DECOMPOSITION WHEN
WEARING CONTACT LENSES; CLOUDING OF LENSES MAY OCCUR. AVOID
PROLONGED EXPOSURE TO EXCESSIVE CONCENTRATIONS.
Exposure Controls
Respiratory Protection:WEAR NIOSH APPROVED SELF CONTAINED BREATHING
APPARATUS AT CONCENTRATIONS >10,000 PPM.
Ventilation:LOCAL EXHAUST: MATERIAL TRANSFER & HANDLING. MECHANICAL:
ALL INDOOR AREAS SHOULD BE VENTILATED.
Protective Gloves:LINED NEOPRENE/LEATHER
Eye Protection:CHEMICAL SAFETY GOGGLES
Other Protective Equipment:NONE
Work Hygienic Practices:DON'T WEAR CONTACT LENSES. DETERMINE THAT
PIPING IS EMPTY BEFORE DOING MAINTENANCE WORK.
Supplemental Safety and Health
PERIODICALLY CHECK CYLINDERS TO ENSURE VALVES AREN'T LEAKING.
Chemical Properties
Boiling Pt:B.P. Text:-72F
Melt/Freeze Pt:M.P/F.P Text:-270F
Vapor Pres:62
Vapor Density:5.1
Spec Gravity:1.57
Solubility in Water:NEGLIGIBLE
Appearance and Odor:ODORLESS, COLORESS GAS
Stability
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, METAL HYDRIDES, OXYGEN.
Stability Condition to Avoid:FLAMES, HOT SURFACES, SMOKING
Hazardous Decomposition Products:TEMPS >1000F, HYDROGEN FLUORIDE,
HYDROGEN BROMIDEE BROMINE, CARBONYL FLUORIDE, CARBONYL BROMIDE.
Disposal
Waste Disposal Methods:RETURN CYLINDERS TO GREAT LAKES CHEMICAL
CORPORATION, EL DORADO, ARKANSAS. NONFLAMMABLE GAS, UN1009. DISPOSE
OF IN ACCORDANCE W/LOCAL, STATE & FEDERAL REGULATIONS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.